Where is your project located? United States
State/Province Connecticut
Nearest City or County New London
How would you like use to size your system? Size by heating demand load and design temperature
Estimated Heating Demand 5.60 kW ( 19101 BTU/hr )
Output of selected heat pump at design temperature (-30C/-22F maximum) 5.9kW
Percentage of demand load requirement produced by heat pump at design temperature (-30C/-22F maximum) 106%
External backup boiler required 6kW
Internal backup boiler required if using Alt Source tank 7.5kW
Heating Demand Load 19101
Heating Demand Load Unit BTU/hr
Selected temperature scale Fahrenheit
Heating Design Temperature 5° F
Arctic heat pump required 035ZA/BE
Comments Comments- Near Passive House build. R40 walls/R60 attic. Man J came in UNDER 2T as follows: Total Heating Required Including Ventilation Air: 19,101 Btuh 19.101 MBH Total Sensible Gain: 17,280 Btuh 87 % Total Latent Gain: 2,604 Btuh 13 % Total Cooling Required Including Ventilation Air: 19,884 Btuh 1.66 Tons (Based On Sensible + Latent) Have currently installed WaterFurnace 2T GSHP (and it does NOT run at full throttle). Would like to upgrade to "variable flow."
Contact by Arctic Agent No

Connect with an Arctic
Heat Expert

No one knows air to water heat pumps like we do!

Have questions about our energy-efficient heating solutions? We're here to help! Whether you need product details, installation support, or assistance with an order, our team is ready to assist you.

Get in touch, no matter where you’re at in your project plans. We’d be so happy to help!

Arctic Heat pumps Logo

LET US HELP

OUR PRODUCTS

RESOURCES

RESOURCES